Using the new CIBSE design summer years to assess overheating in London: Effect of the urban heat island on design
1 January 2015
The new CIBSE design summer years (DSYs) for London Weather Centre, Heathrow and Gatwick in London are now available for three baseline years: 1976, 1989 and 2003. This study tested how these different design summer years impacted the assessment of overheating in a naturally ventilated office in London. Two office designs were tested, an uninsulated and one retrofitted with insulation and night cooling. The choice of baseline year impacted the level of overheating for both the uninsulated and retrofitted models. Tested in the more severe years, 1976 and 2003, the offices experienced the highest levels of overheating. When an office was retrofitted and night cooled, the choice of location had more of animpact on overheating due to the urban heat island effect. London Weather Centre and Heathrow experienced higher levels of overheating than Gatwick. The study highlights the need for designers to carefully consider how the differences between the weather files will impact their overheating assessment depending on their buildings' fabric and ventilation design.Practical application: This study provides initial testing of the how the new CIBSE design summer years impact overheating within a naturally ventilated office in London. Initial analysis of the weather files highlights the differences between locations and baseline years. These differences are then shown to have an impact on overheating depending on the building fabric and ventilation strategy. The results highlight how important it is that practitioners understand how both the weather variables and building and ventilation design will impact the predicted levels of overheating.
Using the new CIBSE design summer years to assess overheating in London: Effect of the urban heat island on design. Building Services Engineering Research and Technology, 36 (2), 115-128.
Virk, G., Mylona, A., Mavrogianni, A., Davies, M. (2015)